Ceiling Insulation
- Ceiling insulation met the R-value requirement in 83% of homes.
- Compliance with the U-Factor requirement was lower, at 58%, due to poor insulation installation quality.
Duct Leakage
- The duct leakage requirement was met in 85% of observations.
- Duct leakage compliance remains an opportunity for improvement.
Envelope Air Leakage
- The requirement was met in 95% of observations.
- There is room for improvement in Climate Zone 3; however, the number of observations is limited.
Foundation & Foundation Insulation
- Basement:
- Not enough observations to report findings.
- Slab Edge:
- Only 28% of the slab edge insulation observations met the requirements, including 16% which pass because they are in Climate Zone 3 where there is no requirement.
- Floor:
- All observations met the R-value requirement; however, U-Factor compliance was 0%, representing an opportunity for improvement.
- Crawlspace:
- All cavity and continuous insulation R-values met or exceeded prescriptive requirements.
- All cavity insulation crawlspace walls failed to meet the U-Factor requirement due to installation quality issues.
Lighting
- Only 54% of homes met the prescriptive lighting requirements.
- A significant number and wide range of observations did not comply.
Wall Insulation
- All observations met or exceeded the R-value requirements for wall cavity insulation.
- Overall U-Factor compliance was 16%; this measure of assembly performance represents a continued opportunity for improvement in the state.
Windows
- All but one observation met the prescriptive SHGC requirement; most exceeded it by a significant margin.
- All observations met the prescriptive window U-Factor requirement, indicating successful implementation across the state.